|  | Industrial Cables |  | |
|  | |||
 Industrial Cables
Industrial Cables
                      H05VV-F/H05VVH2-F
Application and Description
                        
                        H05VV-F/H05VVH2-F cables are suited for medium mechanical stress in damp and wet environments such as refrigerators,
                        washing machines, spin dryers and other appliances, as long as it meets applicable equipment
                        specifications. These cables are also suited for cooking and heating apparatus, provided that the cable
                        does not come into direct contact with the hot parts of the apparatus or with any other heat source. Further
                        applications of this cable include: Fixed installation in furniture, partition walls, decorative covering, and in
                        the hollow spaces of prefabricated building parts. H05VV-F/H05VVH2-F cables are not suitable for outdoor use, industrial (except
                        clothing manufacture) or farming applications. Max operating voltage in single or three phase system is Uo/U
      318/550 volts. In a direct system, max operating voltage is Uo/U 413/825 volts.
Standard and Approval
<HAR>CEI 20-20/5 / 20-35 (EN60332-1) /20-52,
  0.5 - 2.5mm² to BS6500, 4.0mm² to BS7919, 6.0mm² generally to BS7919,
  VDE0281, CENELEC HD21.5, CE low voltage directive 73/23/EEC & 93/68/EEC., ROHS compliant
Cable Construction
 Bare copper fine wire conductor
                         Stranded to DIN VDE 0295 cl. 5, BS 6360 cl. 5, IEC 60228 cl. 5 and HD 383
                        PVC core insulation T12 to VDE-0281 Part 1
                        Color coded to VDE-0293-308
                        Green-yellow grounding (3 conductors and above)
       PVC outer jacket TM2
 
          
Technical Characteristics
Working voltage: 300/500 volts
                        Test voltage: 2000 volts
                        Flexing bending radius: 7.5 x Ø
      Static bending radius: 4 x Ø
 Flexing temperature: -5º C to +70º C
                        Static temperature: -40º C to +70º C
                         Short circuit temperature: +160º C
                       Flame retardant: IEC 60332.1
      Insulation resistance: 20 MΩ x km
 
               
Cable Parameter
| AWG | No. of Cores x Nominal Cross Sectional Area # x mm² | Nominal Thickness of Insulation mm  | Nominal Thickness of Sheath mm  | Nominal Overall Diameter mm  | Nominal Copper Weight kg/Km | |
| H05VV-F | ||||||
| 18(24/32) | 2 x 0.75 | 0.6 | 0.8 | 6.4 | 14.4 | 57 | 
| 18(24/32) | 3 x 0.75 | 0.6 | 6.8 | 21.6 | 68 | |
| 18(24/32) | 4 x 0.75 | 0.6 | 0.8 | 7.4 | 29 | 84 | 
| 18(24/32) | 5 x 0.75 | 0.6 | 0.9 | 8.5 | 36 | 106 | 
| 2 x 1.00 | 0.6 | 0.8 | 6.8 | 19 | 65 | |
| 17(32/32) | 3 x 1.00 | 0.6 | 0.8 | 7.2 | 29 | 79 | 
| 17(32/32) | 4 x 1.00 | 0.6 | 0.9 | 8.0 | 38 | 101 | 
| 17(32/32) | 5 x 1.00 | 0.6 | 0.9 | 8.8 | 48 | 123 | 
| 16(30/30) | 2 x 1.50 | 0.7 | 0.8 | 7.6 | 29 | 87 | 
| 16(30/30) | 3 x 1.50 | 0.7 | 0.9 | 8.2 | 43 | 111 | 
| 16(30/30) | 4 x 1.50 | 0.7 | 1.0 | 9.2 | 58 | 142 | 
| 16(30/30) | 5 x 1.50 | 0.7 | 1.1 | 10.5 | 72 | 176 | 
| 14(30/50) | 2 x 2.50 | 0.8 | 9.2 | 48 | 134 | |
| 14(30/50) | 3 x 2.50 | 0.8 | 1.1 | 10.1 | 72 | 169 | 
| 14(30/50) | 4 x 2.50 | 0.8 | 1.1 | 11.2 | 96 | 211 | 
| 14(30/50) | 5 x 2.50 | 0.8 | 1.2 | 12.4 | 120 | 262 | 
| 12(56/28) | 3 x 4.00 | 0.8 | 1.2 | 11.3 | 115 | 233 | 
| 12(56/28) | 4 x 4.00 | 0.8 | 1.2 | 12.5 | 154 | 292 | 
| 12(56/28) | 5 x 4.00 | 0.8 | 1.4 | 13.7 | 192 | 369 | 
| 3 x 6.00 | 0.8 | 1.1 | 13.1 | 181 | 328 | |
| 10(84/28) | 4 x 6.00 | 0.8 | 1.3 | 13.9 | 230 | 490 | 
| H05VVH2-F | ||||||
| 18(24/32) | 2 x 0.75 | 0.6 | 0.8 | 4.2 x 6.8 | 14.4 | 48 | 
| 17(32/32) | 2 x 1.00 | 0.6 | 0.8 | 4.4 x 7.2 | 19.2 | 57 |