|  | Industrial Cables | ||
Industrial Cables-British Standard
318TQ to BS 6500
Application and Description
318TQ to BS 6500 cables can be used either in dry, humid or wet places or in contact with oil or grease, in weather conditions and under weak mechanical stress, they are suitable for power supply to small appliances in industrial plants, machine shops, heating plates, portable lamps, farming equipment etc. 318TQ to BS 6500 cables are also suitable for caravans and camping equipment. 318TQ is equivalent to harmonized code H05BN4-F.
Cable Construction


- 
        Fine bare copper strands Stranding to BS 6360 CL-5 or IEC 60228 CL-5 EPR(Ethylene Propylene Rubber) rubber EI7 insulation CSP(Chlorosulphonated Polyethylene) outer jacket EM7 
Core Identification
- 
  2cores: Brown, Blue 3cores: Green/Yellow, Brown, Blue 4cores: Green/Yellow, Brown, Black, Grey 5cores: Green/Yellow, Blue, Brown, Black, Grey 6 cores and above: white insulation with black numerals 
Technical Characteristics
- 
                          Working voltage: 300/500 volts Test voltage: 2000 volts Flexing bending radius: 6xOverall diameter Fixed bending radius: 4xOverall diameter Temperature Range: -25º C to +90º C Maximum short circuit temperature: +250º C Flame retardant: IEC 60332.1 Insulation resistance: 20 MΩxkm 
Cable Parameter
| AWG (No of Strands/ Strand Diameter) | No. of Cores x Nominal Cross Sectional Area #xmm² | Nominal Thickness  of Insulation mm | Nominal Thickness  of Sheath mm | Nominal Overall Diameter mm | Nominal Weight kg/km | 
| 3182TQ | |||||
| 18(24/32) | 2x0.75 | 0.6 | 0.8 | 6.5 | 66 | 
| 17(32/32) | 2x1 | 0.6 | 0.9 | 7.1 | 79 | 
| 3183TQ | |||||
| 18(24/32) | 3x0.75 | 0.6 | 0.9 | 7.1 | 80 | 
| 17(32/32) | 3x1 | 0.6 | 0.9 | 7.6 | 94 |